IEC61131 User and Reference Manual
April 22, 2008
189
DIN channel 14 returns measurement status for AIN channel 3.
OFF = channel 0 data is in range.
ON = channel 0 data is in out of range.
DIN channel 15 returns the measurement type for AIN channel 3.
OFF = channel 0 RTD is using 3-wire measurement.
ON = channel 0 RTD is using 4-wire measurement.
DIN channel 16 is reserved for future use.
I/O Connection
Module address
This module is assigned a unique module address between 0
and 15. No other analog input-type module may use this module
address.
Library type
IO complex equipment
AIN sub-module
Data type
Real
Channel type
Input
Number of channels
8
DIN sub-module
Data type
Boolean
Channel type
Input
Number of channels
16