IEC61131 User and Reference Manual
April 22, 2008
369
Inputs
Type
Description
Minute
Integer
Real time clock minutes for absolute time alarm,
valid values 0 to 59.
Number of minutes for elapsed time alarm, valid
values 0 to 1439.
Second
Integer
Real time clock seconds for absolute time alarm,
valid values 0 to 59.
Number of seconds for elapsed time alarm, valid
values 0 to 65535.
Outputs
Type
Description
wakeSource
Integer
The reason the controller left sleep mode. Valid
values are:
1 = real time clock alarm
2 = rising edge of interrupt input
4 = led power switch pushed
8 = counter 0 overflow (every 65536 transitions)
16 = counter 1 overflow (every 65536 transitions)
32 = counter 2 overflow (every 65536 transitions)
256 = Assertion of:
- digital input 0 for SCADAPack 330 or
SCADAPack 350
- Any digital input on SCADAPack LP
- INT/Cntr digital Input on SCADAPack
with 5203/5204 controller board