IEC61131 User and Reference Manual
April 22, 2008
hart1
Send HART command 1
Description
The hart1 function block sends a HART protocol command 1 (“read primary variable”) to a
HART device and processes the response.
Arguments
Set to TRUE to send one HART command. Enable
must then be set to FALSE and back to TRUE to send
another command. Each command is complete when
either the done or error output is TRUE.
The module address of the HART 5904 modem
module. Valid values are 0 to 3.
This must correspond with the module number of a
hart5904 Hart Modem I/O hardware.
The address of the HART device. Valid values are 0 to
15.
TRUE when the enable input is TRUE and a response
is received from the HART device.
FALSE in all other cases.
TRUE when the enable input is TRUE and a there is
an error in the command, or if the HART device fails to
respond to any of the attempts.
FALSE in all other cases.
This output contains the status of the HART command
sent to the HART device.
0 =HART interface module is not communicating
1 =Command ready to send to device
2 =Command sent to device
3 =Response received
4 =No valid response received after all attempts made
5 =HART interface is not ready to transmit